Power Factor Correction Capacitor Failures

Causes, consequences and field solutions

2 min read Dicel Engenharia

The capacitor cell is the most sensitive component in filters and capacitor banks. Surges, resonance with harmonics and reverse energy during switching are the main causes of dielectric puncture — with no recovery and no warranty cover.

ResonanceInrush surgeReverse energy

Terminology

Capacitor cells make up a capacitor; a set of capacitors makes up a bank. The R-L-C assembly constitutes a filter. In filters and capacitors, the most sensitive component is always the capacitor cell.

Basic operating conditions

ParameterLimit
Continuous operating voltageRated + 10% for fluctuations
OvercurrentFundamental + harmonics: 30% intermittent
Inrush currentMaximum 200 × In for 1 ms
Maximum temperature45 °C (ambient + operation)
Switching operations (on/off)Maximum 5,000/year
Expected service lifeUp to 100,000 h under normal conditions

Main failure mode

Cell bulging with operation of the internal fuse — not covered by warranty. Surges above the specified values puncture the dielectric, demetallize the polypropylene, generate gas and expand the can until the fuse opens.
  • Causes: overvoltages, overcurrents and current surges
  • The cell cannot be recovered after puncture

Bank–transformer resonance

The capacitor bank and the transformer go into series resonance with a harmonic present on the network, producing a high current that exceeds the capacitor's limit and punctures the dielectric.

  • Solution: recalculate the bank rating

Inrush current at energization

The line impedance (XL1) is very low — at energization, a current Is1 above 200 × In flows and punctures the dielectric. The inrush-limiting reactor (XL2) limits Is1 to < 200 × In.

  • Special capacitor-duty circuit breakers should only be used where the absence of contactor bounce is guaranteed

Resonance with network harmonics

On networks with nonlinear loads, conventional capacitors can amplify voltage distortion by more than 50%. Detuned filters become indispensable.

Field case — reverse energy at switch-off

Harmonic filter after 6 months in service: 30 kVAr/440 V, 5.67% detuning (Fr 252 Hz), capacitance 411 µF/440 V, inductance L+Lm 0.971 mH. Capacitor voltage was measured for 48 h with four off/on switching operations.

The reactor attenuates the current peak but generates a reverse voltage peak. SPDs, varistors and Zener diodes did not attenuate the reverse energy at switch-off.
  • Solution: special capacitor cells built to withstand the reverse-energy voltage peak
ConditionVoltage surgeDuration
Customer's internal network57% above Vn2 ms
Utility network90% above Vn2 ms
Maximum recorded peak689.5 V2 ms

Main causes of failure

  • Human error due to inadequate training
  • Lack of technical understanding of the phenomenon
  • Insufficient information at the sizing stage