Power Factor Correction Capacitor Failures
Causes, consequences and field solutions
The capacitor cell is the most sensitive component in filters and capacitor banks. Surges, resonance with harmonics and reverse energy during switching are the main causes of dielectric puncture — with no recovery and no warranty cover.
Terminology
Capacitor cells make up a capacitor; a set of capacitors makes up a bank. The R-L-C assembly constitutes a filter. In filters and capacitors, the most sensitive component is always the capacitor cell.
Basic operating conditions
| Parameter | Limit |
|---|---|
| Continuous operating voltage | Rated + 10% for fluctuations |
| Overcurrent | Fundamental + harmonics: 30% intermittent |
| Inrush current | Maximum 200 × In for 1 ms |
| Maximum temperature | 45 °C (ambient + operation) |
| Switching operations (on/off) | Maximum 5,000/year |
| Expected service life | Up to 100,000 h under normal conditions |
Main failure mode
- Causes: overvoltages, overcurrents and current surges
- The cell cannot be recovered after puncture
Bank–transformer resonance
The capacitor bank and the transformer go into series resonance with a harmonic present on the network, producing a high current that exceeds the capacitor's limit and punctures the dielectric.
- Solution: recalculate the bank rating
Inrush current at energization
The line impedance (XL1) is very low — at energization, a current Is1 above 200 × In flows and punctures the dielectric. The inrush-limiting reactor (XL2) limits Is1 to < 200 × In.
- Special capacitor-duty circuit breakers should only be used where the absence of contactor bounce is guaranteed
Resonance with network harmonics
On networks with nonlinear loads, conventional capacitors can amplify voltage distortion by more than 50%. Detuned filters become indispensable.
Field case — reverse energy at switch-off
Harmonic filter after 6 months in service: 30 kVAr/440 V, 5.67% detuning (Fr 252 Hz), capacitance 411 µF/440 V, inductance L+Lm 0.971 mH. Capacitor voltage was measured for 48 h with four off/on switching operations.
- Solution: special capacitor cells built to withstand the reverse-energy voltage peak
| Condition | Voltage surge | Duration |
|---|---|---|
| Customer's internal network | 57% above Vn | 2 ms |
| Utility network | 90% above Vn | 2 ms |
| Maximum recorded peak | 689.5 V | 2 ms |
Main causes of failure
- Human error due to inadequate training
- Lack of technical understanding of the phenomenon
- Insufficient information at the sizing stage