Electrical harmonics and power quality — Dicel guide

What electrical harmonics are, what the harmonic frequencies are, what they cause — and when a plant needs a harmonic filter. Explained in plain language, with references to IEEE 519 and PRODIST.

Understand it in 1 minute

What are harmonics?

Harmonics are current or voltage components at multiples of 60 Hz, generated by equipment that does not draw power sinusoidally — drives, rectifiers, switch-mode power supplies, induction furnaces, LED, chargers and PV inverters.

In practice: the current is no longer a “clean” wave and starts to carry extra frequencies. This raises the RMS value, heats conductors and stresses insulation — even when the energy meter looks normal.

Linear (sinusoidal) current
Nonlinear (distorted) current

THD (Total Harmonic Distortion) sums up this content in a single percentage — the higher it is, the greater the thermal and non-compliance risk (IEEE 519, PRODIST Module 8).

〰️
Harmonics in the current
🔥
Higher RMS current (I²R)
🌡️
Heating
⏳
Reduced service life

An effect documented in standards and engineering literature: harmonics raise losses and temperature in cables, transformers, capacitors, LED drivers and power electronics.

Check IEEE 519 limits →
Order by order

Harmonic frequencies: 3rd, 5th, 7th and the rest

The frequency of each harmonic is its order multiplied by the supply frequency. In Brazil the supply is 60 Hz: the 3rd harmonic is at 180 Hz, the 5th at 300 Hz, the 7th at 420 Hz. Each order has its own origin and effect — which is why a measurement shows the spectrum, not just the THD.

OrderFrequency (60 Hz supply)SequenceTypical sourceTypical effect
2nd120 HzNegativeHalf-wave rectification, arc furnaces, transformer energizationUsually small, but can resonate with filters and capacitors
3rd180 HzZeroSingle-phase loads: switch-mode power supplies, LED, computers, electronic ballastsAdds up in the neutral, which can carry more current than the phases; heats transformers
5th300 HzNegative6-pulse rectifiers: variable-frequency drives, UPS systems, induction furnacesOpposing torque in motors; resonance with capacitor banks
7th420 HzPositive6-pulse rectifiersHeating of cables, motors and transformers
9th540 HzZeroNonlinear single-phase loadsNeutral current
11th660 HzNegative6- and 12-pulse rectifiersAdditional losses and interference with sensitive electronics
13th780 HzPositive6- and 12-pulse rectifiersAdditional losses and interference with sensitive electronics

Rule of thumb: a p-pulse converter mainly generates the orders k·p ± 1 — 5th and 7th, 11th and 13th for a 6-pulse rectifier. Frequencies that are not integer multiples of 60 Hz are interharmonics. Even harmonics matter too: see the article Even Harmonics: Can They Be Ignored?

Where they appear

Where harmonics appear — and why they are increasing

Power electronics have changed the load profile. Drives, LED, distributed generation and chargers put harmonics on networks that used to carry only linear loads — and utility requirements are following.

IndustryFurnaces, drives, data centers, substations — the problem shows up as downtime and equipment failures
DG + time-of-use tariffInverters, electronic loads — the problem often goes unnoticed
Critical infrastructureAirports, hospitals, telecom — EMC and continuity

What has changed in recent years

  • Drives, inverters and rectifiers in motors, solar, EVs and HVAC
  • Distributed generation — millions of units connected to the distribution network
  • LED and switch-mode power supplies replacing linear loads
  • Regulation — PRODIST, RISE, trends in the ten-year plan (PDE 2035)

PDE 2035 and the future of the grid

The Ten-Year Energy Expansion Plan 2035 (EPE/MME) projects an energy mix with far more DG, storage and dispersed loads. More inverter-connected points on the grid means more attention to power quality — not just generation.

  • Distribution utilities are likely to monitor THD and disturbances more strictly
  • Prosumers may face evolving connection and compliance requirements
  • Power quality measurement is no longer a topic for large industry alone

Official EPE documents — PDE 2035 →

Already in force: PRODIST and IEEE

PRODIST Module 8 (ANEEL) sets power quality limits on the network — including voltage harmonic distortion. Installations that affect the network may need a RISE.

  • IEEE 519-2022 — current THD limits at the PCC
  • IEEE 1159-2019 — power quality monitoring
  • CIGE — the plant's internal energy management committee

Dicel Class A measurements and RISE →

How the problem shows up

Two consumer profiles

Industry — the problem has already surfaced

Large orders of magnitude, immediate effect

A substation trips when an induction furnace comes online. Protection operates — unplanned downtime, production halted, the technical team left without a clear diagnosis. Measurements show high THD, inrush and interaction with capacitor banks.

“The symptom is obvious. The cause calls for Class A measurement and filter design — which is where Dicel has been working for decades.”
Harmonic distortion filters

DG and residential — the problem can be silent

Time-of-use tariff, solar, electronic loads

An installation with distributed generation and a time-of-use tariff: an apparently normal kWh bill, with reactive power not always visible on residential metering. Yet inverters and nonlinear loads inject and absorb harmonics — energy that turns into heat in wiring, LED drivers and electronics, with no warning to the consumer.

“It is worth investigating before it becomes a hidden cost or equipment damage.”
Request assessment
Technical basis

Heat, losses and service life: the physical effect of harmonics

What harmonics cause most, beyond additional energy consumption (and cost), is heating in conductors and equipment. Engineering literature documents the reduced service life of insulation and electronic components at elevated temperature.

Joule losses (I²R)

Harmonics increase the RMS value of the current. Conductor losses grow with the square of the current — cables, busbars and transformers run hotter for the same “perceived” load.

Insulation and transformers

Distorted currents require a suitable K-factor for the transformer. Loading above the K rating accelerates insulation aging — industry rule of thumb: service life is reduced by ~50% for every 10°C above the rated class.

Capacitors and resonance

Capacitor banks in environments with THD can go into resonance, amplifying harmonic currents. That is why detuning (e.g. 5.67%) and passive filters are specified on the basis of prior measurement.

Electronics and lighting

LED drivers, switch-mode power supplies and power semiconductors suffer from ripple and additional heating. Electrolytic capacitor life and junction temperature deteriorate with a degraded waveform.

References and Dicel materials

From theory to design

Capacitor, passive or active — which path?

Once the problem is clear (harmonics, PF, resonance), the next decision is topology: the one the measurement justifies, not necessarily the most expensive.

Capacitor / PFC

Corrects power factor on linear loads. With high THD it can resonate and worsen distortion.

Detuned passive ★

Reactor + capacitor: PFC and harmonic mitigation with anti-resonance. Core of the Dicel catalog.

Active / hybrid

Power electronics injects cancelling current (AHF) or combines with passive stages. Ideal when the load is highly dynamic.

Full guide: passive × active → View passive filters Measure before sizing
FAQ

Frequently asked questions about electrical harmonics

What are harmonic frequencies?

They are integer multiples of the supply frequency. On a 60 Hz supply, the 2nd harmonic is at 120 Hz, the 3rd at 180 Hz, the 5th at 300 Hz and so on. They appear when a load draws current non-sinusoidally.

Harmonics or harmonic distortion: which term is right?

Both describe the same phenomenon. “Harmonics” are the individual frequency components; “harmonic distortion” is their combined effect on the waveform. Standards and manufacturers use both.

What causes harmonics on the electrical network?

Nonlinear loads: variable-frequency drives, rectifiers, UPS systems, induction and arc furnaces, LED lighting, switch-mode power supplies, electric vehicle chargers and PV inverters.

What are the effects of harmonics?

Heating of cables, transformers and motors, capacitor failure through resonance, nuisance tripping of protection, high neutral current, failures in sensitive electronics and the risk of exceeding the IEEE 519 and PRODIST limits.

Do harmonics increase the electricity bill?

They increase losses in conductors and transformers, which are paid for as kWh. They can also damage the capacitor bank and make the power factor drop, which leads to charges for excess reactive energy (UFER).

How are harmonics measured?

With a Class A power quality analyzer, which records the voltage and current spectrum order by order. Dicel recommends measuring for seven consecutive days, including a weekend, at the point of common coupling and at the main loads.

What is the acceptable limit for harmonic distortion?

It depends on the standard and the voltage level. For systems up to 1 kV, IEEE 519 recommends total voltage distortion of up to 8% and up to 5% per individual harmonic; the current distortion limit depends on the ratio between the short-circuit current and the load current. In Brazil, PRODIST Module 8 sets the voltage distortion limits.

How can harmonics be reduced or eliminated?

With a detuned passive harmonic filter, an active filter or a combination of the two, sized from the measurement. Line reactors and 12-pulse converters also reduce generation at the source.

Next step: harmonic filters — types and when to use them or Class A measurement.