Interactive calculators for capacitor sizing, harmonic checks and electrical parameter lookup.
* Approximate results for initial reference. Assumptions and tables fixed in this version on 13/10/2026, without automatic updates. Initial values are editable examples; check tariffs on your bill and equipment data in the manufacturer’s catalogue. They do not replace installation design.
Enter active power, the current PF and the target PF to estimate the correction in kVAr. The displayed commercial rating is a table reference, not an installation specification. Model for linear loads.
Correction: Q = P × [tan(φ₁) − tan(φ₂)]. The theoretical reduction in upstream conductor losses is [1 − (current PF / target PF)²] × 100, assuming constant active power, voltage and resistance, with no harmonic distortion. The percentage refers to the target PF, before rounding to a commercial rating.
This percentage does not represent savings on the electricity bill or a reduction in total consumption. For nonlinear loads, harmonic analysis is required before selecting compensation.
Technical reference: conductor losses — Schneider Electric (in English)
Select the power in HP and the number of poles — get the recommended kVAr and the percentage reduction in supply current.
Unloaded transformers consume reactive power. Consult approximate table values; use the model’s catalogue for sizing.
Simplified reference at the point of common coupling (PCC). Icc is short-circuit current; IL is maximum-demand fundamental current. The current table covers only systems from 120 V to 69 kV.
Need to check whether your plant is compliant? Dicel performs Class A electrical measurements and issues reports with IEEE 519/2022 analysis and RISE per PRODIST.
Resistance and reactance per km: reference values depend on the model and installation conditions. Search by code or conductor size.
| Code | Material | Size | R (Ω/km) | X (Ω/km) | |Z| (Ω/km) |
|---|---|---|---|---|---|
| A04 | Aluminum | 04 AWG | 1.5285 | 0.3603 | 1.5704 |
| A02 | Aluminum | 02 AWG | 0.9632 | 0.3420 | 1.0221 |
| A10 | Aluminum | 1/0 AWG | 0.6045 | 0.3249 | 0.6863 |
| A20 | Aluminum | 2/0 AWG | 0.4791 | 0.3155 | 0.5737 |
| A40 | Aluminum | 4/0 AWG | 0.3020 | 0.2983 | 0.4245 |
| A33 | Aluminum | 336,4 MCM | 0.1907 | 0.2765 | 0.3359 |
| C06 | Copper | 06 AWG | 1.3765 | 0.3822 | 1.4286 |
| C02 | Copper | 02 AWG | 0.5561 | 0.3467 | 0.6553 |
| C10 | Copper | 1/0 AWG | 0.3504 | 0.3257 | 0.4784 |
| C20 | Copper | 2/0 AWG | 0.2783 | 0.3170 | 0.4218 |
| P12 | Multiplex | 120 mm² | 0.2940 | 0.0942 | 0.3087 |
| P25 | Multiplex | 25 mm² | 1.3900 | 0.1055 | 1.3940 |
| P35 | Multiplex | 35 mm² | 1.0100 | 0.1138 | 1.0164 |
| P50 | Multiplex | 50 mm² | 0.7440 | 0.1092 | 0.7520 |
| P70 | Multiplex | 70 mm² | 0.5680 | 0.0945 | 0.5758 |
| M63 | Triplex | 06 AWG / 16 mm² | 2.6550 | 0.0999 | 2.6569 |
| M64 | Quadruplex | 06 AWG / 16 mm² | 2.6550 | 0.1189 | 2.6577 |
| M43 | Triplex | 04 AWG / 25 mm² | 1.6710 | 0.0963 | 1.6738 |
Simulate a simplified scenario for reducing excess reactive energy charges and the simple payback of the correction investment.
* Simplified model for Brazilian Group A consumers: consumption × (0.92 ÷ PF − 1) × tariff. Assumes constant consumption and PF in chargeable periods, corrected to PF 0.92. The initial tariff of R$ 0.45/kWh is fictitious, not a current tariff. The annual value repeats 12 identical months; payback divides investment by this annual value. Excludes reactive demand, taxes, electrical losses, operating costs and hourly variation. Active power is used only to estimate kVAr.
Organize documents and studies for the electrical system impact report (RISE). Checking items tracks preparation only; it does not establish compliance. Requirements depend on the distributor and the case.
Historical reference: RGE/CPFL guidance, version 4 of 18/03/2010. Check your distributor’s current requirements before filing.
Dicel issues complete RISE reports with Embrasul RE8000 measurements, IEEE 519/2022 analysis and filter recommendations. Request a quote →