Technical Tools

Interactive calculators for capacitor sizing, harmonic checks and electrical parameter lookup.

FOR NONLINEAR LOADS Power factor correction alone does not solve harmonic distortion. Drives, furnaces, LED, DG and switch-mode power supplies require measurement and, often, a detuned filter — not just a capacitor.

* Approximate results for initial reference. Assumptions and tables fixed in this version on 13/10/2026, without automatic updates. Initial values are editable examples; check tariffs on your bill and equipment data in the manufacturer’s catalogue. They do not replace installation design.

Power Factor Correction Calculator

Enter active power, the current PF and the target PF to estimate the correction in kVAr. The displayed commercial rating is a table reference, not an installation specification. Model for linear loads.

Value: 0.70
Value: 0.95
69.2
kVAr required
70
Commercial reference (kVAr)
45.7%
Theoretical reduction in Joule losses
The indicated capacitor is only the nearest commercial rating, not an installation specification. The design must account for voltage, operating stages and harmonics.
How to interpret this estimate

Correction: Q = P × [tan(φ₁) − tan(φ₂)]. The theoretical reduction in upstream conductor losses is [1 − (current PF / target PF)²] × 100, assuming constant active power, voltage and resistance, with no harmonic distortion. The percentage refers to the target PF, before rounding to a commercial rating.

This percentage does not represent savings on the electricity bill or a reduction in total consumption. For nonlinear loads, harmonic analysis is required before selecting compensation.

Technical reference: conductor losses — Schneider Electric (in English)

Motor Capacitor Sizing

Select the power in HP and the number of poles — get the recommended kVAr and the percentage reduction in supply current.

1
Recommended kVAr
24%
Current reduction
1800 RPM
Rated speed
Approximate reference table values. Check the model, voltage and load condition in the catalogue before sizing.

Power Factor Correction for Transformers

Unloaded transformers consume reactive power. Consult approximate table values; use the model’s catalogue for sizing.

4.5 kVAr
No-load reactive power
5 kVAr
Approximate commercial reference*
Approximate reference table values. Check the model, voltage and load condition in the catalogue before sizing.

Harmonic Distortion Limits — IEEE 519

Simplified reference at the point of common coupling (PCC). Icc is short-circuit current; IL is maximum-demand fundamental current. The current table covers only systems from 120 V to 69 kV.

Harmonic current limits (% of IL)

3 ≤ h < 11
10%
11 ≤ h < 17
4.5%
17 ≤ h < 23
4%
23 ≤ h < 35
1.5%
35 ≤ h ≤ 50
0.7%
TDD (%)
12%
V ≤ 1 kV: Maximum individual distortion 5% · Maximum THD 8%
Reference: IEEE 519-2022. Displayed current ranges apply to odd harmonics; consult the standard for even harmonics, generation and exceptions. This table does not certify compliance.

Need to check whether your plant is compliant? Dicel performs Class A electrical measurements and issues reports with IEEE 519/2022 analysis and RISE per PRODIST.

Cable and Wire Table — Secondary Network

Resistance and reactance per km: reference values depend on the model and installation conditions. Search by code or conductor size.

Code Material Size R (Ω/km) X (Ω/km) |Z| (Ω/km)
A04 Aluminum 04 AWG 1.5285 0.3603 1.5704
A02 Aluminum 02 AWG 0.9632 0.3420 1.0221
A10 Aluminum 1/0 AWG 0.6045 0.3249 0.6863
A20 Aluminum 2/0 AWG 0.4791 0.3155 0.5737
A40 Aluminum 4/0 AWG 0.3020 0.2983 0.4245
A33 Aluminum 336,4 MCM 0.1907 0.2765 0.3359
C06 Copper 06 AWG 1.3765 0.3822 1.4286
C02 Copper 02 AWG 0.5561 0.3467 0.6553
C10 Copper 1/0 AWG 0.3504 0.3257 0.4784
C20 Copper 2/0 AWG 0.2783 0.3170 0.4218
P12 Multiplex 120 mm² 0.2940 0.0942 0.3087
P25 Multiplex 25 mm² 1.3900 0.1055 1.3940
P35 Multiplex 35 mm² 1.0100 0.1138 1.0164
P50 Multiplex 50 mm² 0.7440 0.1092 0.7520
P70 Multiplex 70 mm² 0.5680 0.0945 0.5758
M63 Triplex 06 AWG / 16 mm² 2.6550 0.0999 2.6569
M64 Quadruplex 06 AWG / 16 mm² 2.6550 0.1189 2.6577
M43 Triplex 04 AWG / 25 mm² 1.6710 0.0963 1.6738

Savings Estimator — UFER and Reactive Energy

Simulate a simplified scenario for reducing excess reactive energy charges and the simple payback of the correction investment.

Value: 0.78 · Reference: 0,92
R$ 48.461,54
Annual reduction in this scenario*
94.1
kVAr for PF 0,92
R$ 4.038,46
Monthly reduction in this scenario*
0.5 years
Simple payback in this scenario*
Approximate scenario for reducing excess reactive energy charges; not a bill forecast or guaranteed savings. See the assumptions below.

* Simplified model for Brazilian Group A consumers: consumption × (0.92 ÷ PF − 1) × tariff. Assumes constant consumption and PF in chargeable periods, corrected to PF 0.92. The initial tariff of R$ 0.45/kWh is fictitious, not a current tariff. The annual value repeats 12 identical months; payback divides investment by this annual value. Excludes reactive demand, taxes, electrical losses, operating costs and hourly variation. Active power is used only to estimate kVAr.

ANEEL — REN 1000/2021, art. 304

Initial RISE preparation checklist

Organize documents and studies for the electrical system impact report (RISE). Checking items tracks preparation only; it does not establish compliance. Requirements depend on the distributor and the case.

Checklist progress
0 of 12 items (0%) · Essential: 0/8

Historical reference: RGE/CPFL guidance, version 4 of 18/03/2010. Check your distributor’s current requirements before filing.

RGE / CPFL — RISE

Initial preparation. Organize the documents and studies relevant to your case.

Dicel issues complete RISE reports with Embrasul RE8000 measurements, IEEE 519/2022 analysis and filter recommendations. Request a quote →