Harmonic Filters (Distortion Filters)

Detuned passive filters with simultaneous power factor correction

Detuned passive line — PFC plus harmonic mitigation. Why passive, and when does active fit? →

Guide: what a harmonic filter is and when to use one →

BT 1.1.1
BT 1.1.1
  • CD 100 / CD 101 enclosure
  • 2 to 72 kVAr / 220 to 480 V
  • Forced ventilation and LED

Application

  • Panel mounting
  • Local correction
  • High distortion levels
Technical details — BT 1.1.1

Detuned passive filters with simultaneous PF correction. CD100/CD101 series with three-phase cells, forced ventilation and LED monitoring.

CD100 and CD101 series

  • Voltages: 220 – 380 – 440 – 480 – 525 V (line-to-line)
  • 2 to 30 kVAr — CD100 enclosure (510×247×406 mm)
  • 35 to 60 kVAr — CD101 enclosure (525×291×560 mm)
  • Weight: 15 to 55 kg depending on rating
  • Detuning factor to order, according to THD

Tables by rated voltage

Detuned filters — 220 V
Detuned filters — 220 V
Detuned filters — 380 V
Detuned filters — 380 V
Detuned filters — 440 V
Detuned filters — 440 V
Detuned filters — 480 V
Detuned filters — 480 V
BT 1.1.2
BT 1.1.2
  • CD 100/101/103 enclosure, IP-54
  • 5 to 72 kVAr / 220 to 525 V

Application

  • Outdoor use IP54
  • Wind turbines
  • Generator sets
  • Automatic banks
Technical details — BT 1.1.2

RLC filter with built-in switching, protection, timing and heat exchange. Technology with 10-year traceability (IEC 831).

Advantages

  • Attenuates THD and corrects PF simultaneously
  • RLC assembly adjusted in the laboratory
  • 10-year traceability — cell service life
  • Thermostat-controlled forced ventilation of the reactor (40°C)
  • Options: fuse monitoring, stalled-fan detection

Installation precautions

  • Do not install on the same network as conventional capacitors — this alters the detuning factor and can burn out the reactor
  • Do not obstruct convection; in an automatic bank, ventilate each column (45°C thermostat)
  • Clean, ventilated location; do not tip over — the reactor is heavy

Tables by rated voltage

Technical specifications
Technical specifications
BT 1.2.1
BT 1.2.1
  • Enclosures for 8 to 20 filters
  • 0.1 to 1.4 MVAr / 220 to 600 V

Application

  • FHT automatic banks
  • CD-series filters on rails
Technical details — BT 1.2.1

Basic specifications

  • Voltages: 220 – 380 – 440 – 480 – 525 – 600 V
  • Ratings: 0.1 to 1.4 MVAr
  • Filters on ball rollers, mounted on rails
  • Thermostats in the filters and in the panel
  • Drawers for fan inspection
BT 1.5.1
BT 1.5.1
  • Gas-discharge lamp lighting
  • up to 12 lamps / 400 W

Application

  • Systems with ballasts
  • Generator-fed networks
Technical details — BT 1.5.1

PF correction (0.95) and up to 40% THD attenuation. Do not install a capacitor at the ballast — it amplifies harmonics.

Specifications

  • Three-phase + neutral, 220 V
  • up to 12 gas-discharge lamps of 400 W
  • Protection by thermal-magnetic circuit breaker
  • Control by timed contactor, 0–100 s
BT 1.6.1
BT 1.6.1
  • CD 91 enclosure
  • 0.4 to 3 kVAr / 127 to 380 V

Application

  • FRCFP residential use
  • UFER reduction
  • Filtering at the home service entrance
Technical details — BT 1.6.1

FRCFP: filters power at the service entrance, corrects the PF of household appliances and attenuates harmonics. Install after the main circuit breaker, always switched on.

FRCFP specifications

  • Single-phase, two-phase or three-phase — 127, 220 or 380 V
  • 0.4 to 3 kVAr — 220×200×100 mm — 1.2 kg
  • Built-in circuit breaker protection
  • Reduces burnt-out lamps and damage to TVs and microwave ovens