Passive, active or hybrid — which filter makes sense?

A capacitor bank alone, a detuned passive filter and an active filter (AHF) solve different problems. Dicel starts with measurement and engineering, not with the equipment.

Why compare

An active filter is not always the answer. The plant needs the right solution.

With harmonics and poor power factor, three options land on the engineer’s or buyer’s table:

  1. Capacitor bank — corrects PF on linear loads; with high THD it can worsen resonance.
  2. Passive filter (detuned / tuned) — L+C (+R), PFC and harmonic mitigation with a fixed topology.
  3. Active filter (AHF) — power electronics injects cancelling current in near real time.

There is also the hybrid (passive + active) and relatives: SVG (dynamic reactive), drive-side sine filters, HF EMC/EMI.

← Back to the power quality guide

1. Symptom (reactive penalty, failed capacitors, protection, THD)
2. Class A measurement + harmonic spectrum
3. Choose topology (passive / active / hybrid)
4. Size, install, validate (IEEE 519 / PRODIST)

Skipping step 2 is the main reason “filter installed, problem remains” — passive or active.

Measurements & RISE →
Three paths

Capacitor · Passive · Active

Each has different components, cost and risk. The “best” one matches the measurement and the plant’s life-cycle budget.

1. Capacitor / PFC bank

What it does: injects capacitive reactive power, raises PF, often cuts reactive penalties.

When: mostly linear loads, low THD, no resonance history.

Risk: with harmonics, C can resonate with the network and amplify THD — capacitors fail, cables overheat.

Capacitor catalog →

2. Detuned passive ★ Dicel

What it does: a series reactor with C detunes resonance (e.g. 5.67% / 7%); attenuates harmonics and corrects PF at once.

When: industrial plant with THD and PFC need; relatively stable load profile known from measurement.

Strength: robustness, typically lower cost than AHF, conventional maintenance, decades of application.

Distortion filters →

3. Active (AHF / ASVG)

What it does: converter measures distorted current and injects the “anti-current” on several orders; SVG focuses on dynamic reactive power.

When: highly variable loads, many orders, multiple pollution points, or a spec that requires AHF.

Trade-off: higher flexibility and price; depends on CTs, setpoints, firmware and commissioning.

Consulting to specify →

Decision

When to use each approach

Situation Tendency Why
Low PF, low THD, linear loadsCapacitor / PFC bankSimple and enough if there is no resonance
PFC + moderate/high THD, “stable” plantDetuned passiveAnti-resonance + reactive; good cost/benefit
Dominant fixed harmonic order (e.g. strong 5th)Tuned passive (L-C branch)Absorbs the target order efficiently
Loads switch on/off constantly, wide spectrumActive (AHF)Adapts in real time across many orders
Large reactive base + dynamic harmonic peaksHybrid (passive + active)Passive holds the base; active cleans the rest
Drive/inverter → motor (PWM, dv/dt)LC sine filter (load side)Different problem — does not replace busbar AHF
HF noise, automation, EMC certificationEMC/EMIDifferent frequency band than 5th–50th harmonics
“Sales said only active works”Measure firstMany plants succeed with a well-sized passive filter
Inside the enclosure

Typical components — passive and active

Useful for specs, RFQs and supplier talks. Active units also have a small passive stage at the output (L/LCL) to filter converter PWM.

Passive (detuned / tuned)

  • Power capacitors (film cells, delta/wye)
  • Detuning reactor in series with C (e.g. 5.67%, 7%, 14%)
  • Tuning reactor in tuned filters (5th, 7th, 11th…)
  • Damping resistor (damped / type-C filters)
  • Contactors or thyristors (automatic staged bank)
  • Protection — fuses, breaker, thermal, ventilation
  • PF controller + CTs (if automatic)
  • Enclosure, busbars, optional SPD / surge protection

At Dicel: distortion filters, capacitors, inductors.

Active (AHF / SVG)

  • Power inverter (IGBT/SiC) three-phase
  • DC-link capacitors (DC bus)
  • Output L or LCL filter (removes PWM switching)
  • CTs on load and/or grid + voltage sensors
  • DSP / control (PLL, harmonic extraction)
  • Auxiliary supplies and gate drivers
  • MCCB, contactor, fuses on the input
  • Cooling, HMI, communication (Modbus/Ethernet)

SVG uses similar electronics focused on dynamic reactive power. Hybrid combines passive branches + an active module.

Comparison

Passive × active in one table

Passive Active (AHF)
PrincipleL/C/R, frequency impedanceOpposite current injection
FlexibilityLower — fixed by designHigh — many orders, variable load
PFC + harmonicsDetuned does both wellAHF/SVG can as well
Typical costLow to mediumMedium to high
MaintenanceConventional (contactors, C, L, cleaning)Electronics + firmware + CTs
Risk if misappliedResidual resonance, under/over sizingWrong CT, saturation, setpoint, install point
What Dicel does

What Dicel supplies — and when measurement calls for something else

Dicel designs and supplies passive solutions (detuned filters, PFC, sine-wave, EMC/EMI, reactors) with technical bulletins and application validation. The work starts with measuring, explaining the result against the standard and sizing.

  • Passive catalog with photos and technical bulletins
  • Class A measurement (Embrasul / Eberle) and RISE
  • Consulting, courses and lectures

When the load profile calls for active or hybrid, Dicel carries out the assessment and the engineering specification so that the right solution goes into the project.

Active or hybrid — what to check before specifying

An active filter is more than buying a module. Before specifying an AHF, SVG or hybrid solution, check:

  • Modeling — harmonics, short-circuit, resonance, IEEE 519 at the PCC
  • Power electronics — IGBT, DC link, LCL, losses, thermal derating
  • Control — PLL, harmonic extraction, stability with several actives on the same bus
  • Instrumentation — CT selection and installation (ratio, saturation, load vs grid side)
  • Protection and selectivity — coordination with breakers and ultra-fast fuses
  • EMC and installation — grounding, cables, panel layout
  • Commissioning — setpoints, modes (harmonics / reactive / balancing), Class A validation
  • Standards and safety — converter IEC, testing, warranty responsibilities

Measurement and design come before technology: active or hybrid complements engineering, it does not replace it.

Next step

Recommended flow at Dicel

1. MeasureClass A, spectrum, PF, events
2. InterpretIEEE 519, PRODIST, resonance
3. SizePassive from catalog or active/hybrid spec
4. ValidatePost-install and compliance
Passive filters (distortion) Full catalog Measurements & RISE IEEE 519 tool Talk to engineering

Related reading: Power quality · Article AT5 — capacitor failures · BT 1.1.1 — detuned filters

Do not choose the technology in the dark

Class A measurement + report with recommendations — industrial or DG investigation. Then we size the right filter.