Applying Filters to Variable-Frequency Drives
dv/dt (EMC/EMI) filters vs. LC/LCL sinusoidal filters
Filters at the output of drives fall into two types: dv/dt or EMC/EMI filters (motor protection with up to 100 m of cable) and LC/LCL sinusoidal filters (pure sine wave, cables up to 300 m). The choice depends on the application, cable length and acoustic requirements.
dv/dt or EMC/EMI filters
They protect the motor against arcing by reducing the voltage peaks responsible for stator insulation failure. They allow the use of motors not designed for drive operation (e.g. rewound motors). Cable between drive and motor of up to 100 m, shielded or not.
- Acts on voltage peaks and on static voltage at the bearings
- Eliminates audible noise from motor cables up to 100 m
- Attenuates frequencies above the switching frequency and reverse energy from the supply
- Smaller, lighter and cheaper than sinusoidal filters
| Specification | Value |
|---|---|
| Voltage | up to 520 VAC |
| Current | 8–600 A (paralleled for higher current) |
| Motor frequency | up to 60 Hz without derating; 100/120 Hz with derating |
| Temperature | -25 °C to 40 °C |
| Switching frequency | 1.5–8 kHz |
| Overload | 150 % for 60 s every 10 min |
Applications — dv/dt filters
- Regenerative braking with short cables (< 15 m)
- Motors in harsh environments or at high temperatures
- Risk of arcing (jumping arcs)
- Old, reconditioned or general-purpose motors
- Side-by-side mounting with the converter
LC or LCL sinusoidal filters
Designed for installation between drive and motor. They completely eliminate PWM noise and allow cables of up to 300 m (shielded).
- Protects the motor against voltage peaks — extends service life
- Attenuates PWM harmonic distortion — reduces motor losses
- Eliminates switching (PWM) noise from the motor
- Reduces losses in the drive's semiconductors with long cables
- Reduces bearing currents — extends motor service life
- Reduces electromagnetic emissions from the cables
Applications — sinusoidal filters
- Frequent regenerative braking
- Conventional or reconditioned motor with a drive
- Elimination of PWM acoustic noise
- Motor cables up to 300 m (shielded or unshielded)
- Where the motor maintenance interval must be extended
- Note: larger, heavier and more costly than dv/dt filters
| Specification | Value |
|---|---|
| Voltage | up to 520 VAC, 60 Hz |
| Current | 8–600 A |
| Maximum cable length | 300 m |
| Switching frequency | 1.5–8 kHz |
| Overload | 150 % for 60 s every 10 min |
Sizing
Correct sizing requires power quality and power flow measurements. Request Technical Bulletin BT 5.2: engenharia@dicelrs.com.br